Manuel d'utilisation du compteur d'énergie triphasé bidirectionnel Acrel DTSD1352

Model: DTSD1352 | Brand: Acrel (Manufactured by TGLGTQPX)

1. Introduction

This manual provides comprehensive instructions for the installation, operation, and maintenance of the Acrel DTSD1352 Three Phase Bidirectional Energy Meter. This device is designed for accurate measurement of three-phase energy consumption and generation, featuring RS485 communication for integration into monitoring systems. Please read this manual thoroughly before installation and operation to ensure safe and efficient use.

2. Consignes de sécurité

AVERTISSEMENT : risque de choc électrique !

  • L'installation et la maintenance ne doivent être effectuées que par des électriciens qualifiés.
  • Ensure all power is disconnected before installing or servicing the meter.
  • Ne touchez pas aux terminaux sous tension.
  • Verify correct wiring connections to prevent damage to the meter or electrical system.
  • The meter must be installed in a dry, well-ventilated area, free from excessive dust, corrosive gases, and direct sunlight.

3. Produit terminéview

The Acrel DTSD1352 is a compact and robust three-phase multi-function energy meter. It features a clear LCD display for real-time data, intuitive control buttons, and various connection terminals.

Devant view of the Acrel DTSD1352 energy meter showing the LCD display, control buttons, and terminal connections.

Figure 3.1 : Devant view of the DTSD1352 meter. This image displays the main LCD screen showing power readings (e.g., 0.00 kW), the "SET" button, and three orange arrow buttons for navigation. Terminal blocks are visible at the top and bottom for electrical connections.

Incliné view of the Acrel DTSD1352 energy meter, showing the side profile and additional terminal details.

Figure 3.2 : Incliné view of the DTSD1352 meter. This perspective highlights the compact design and the various input/output terminals on the top and bottom, as well as the side labeling for model identification.

4. Spécifications

The following table outlines the key technical specifications of the Acrel DTSD1352 energy meter. For detailed information, refer to the product datasheet.

Table of technical specifications for the Acrel DTSD1352 energy meter, including voltage, current, measurement performance, pulse, communication, outline, and environment details.

Figure 4.1 : Detailed technical specifications. This image presents a table covering various parameters such as reference voltage (3*57.7/100V, 3*220/380V, 3*380V), reference frequency (50Hz), maximum current (6A, 80A), accuracy (Class 0.5S), communication interface (RS485, MODBUS-RTU), dimensions (127*88*70 mm), and environmental conditions (operating temperature -25~55℃, humidity ≤95%).

Tableau 4.1 : Spécifications générales
ParamètreValeur
Vol de référencetage3*57.7/100V, 3*220/380V, 3*380V
Fréquence de référence50 Hz
Courant maximal6A, 80A (depending on model)
Accuracy of active kWhClasse 0.5S
Interface de communicationRS485
Protocole de communicationMODBUS RTU
Dimensions (L x l x H)127 mm x 88 mm x 70 mm
Température de fonctionnement-25℃ à 55℃
Température de stockage-40℃ à 70℃
Humidité≤95% (pas de condensation)
Altitude<2000 m
Poids de l'article7.1 onces (environ 200 g)

5. Installation et câblage

Proper installation and wiring are critical for the accurate and safe operation of the DTSD1352 meter. Refer to the diagrams below for connection methods.

Wiring diagrams for the Acrel DTSD1352 energy meter, showing both direct connection (3P4W) and connection via Current Transformers (CTs).

Figure 5.1 : Wiring diagrams. This image illustrates two primary wiring methods: a 3-phase 4-wire (3P4W) direct connection where power lines (A, B, C, N) connect directly to the meter, and a connection via Current Transformers (CTs) for higher current applications, showing the CTs connected to the respective phase lines and then to the meter.

5.1 Direct Connection (3P4W)

For direct connection, ensure the phase lines (A, B, C) and neutral (N) are connected to the corresponding terminals on the meter. This method is typically used for lower current applications where the meter can directly handle the load current.

  • Connect Phase A to terminal 'A'.
  • Connect Phase B to terminal 'B'.
  • Connect Phase C to terminal 'C'.
  • Connect Neutral to terminal 'N'.
  • Assurez-vous que toutes les connexions sont sécurisées et correctement isolées.

5.2 Connection via Current Transformers (CTs)

For higher current applications, the DTSD1352 meter can be connected via external Current Transformers (CTs). This method scales down the current to a measurable level for the meter.

  • Install the CTs on each phase line (A, B, C).
  • Connect the secondary windings of the CTs to the corresponding current input terminals (e.g., Ia*, Ia, Ib*, Ib, Ic*, Ic) on the meter.
  • Ensure the polarity of the CTs is correct (P1/K to the source side, P2/L to the load side, and S1/S2 to the meter). Incorrect polarity will result in inaccurate readings.
  • Connectez le voltage inputs (Ua, Ub, Uc, N) directly from the respective phases and neutral to the meter.
  • It is recommended to install a fuse on the voltage input lines for protection.

Important: Always ensure the CT secondary circuit is closed before applying power to the primary circuit. Never open the secondary circuit of a live CT.

6. Fonctionnement

Once installed and powered, the DTSD1352 meter will automatically begin measuring. The LCD display shows various parameters, which can be navigated using the control buttons.

6.1 Navigation de l'écran

  • Écran LCD : Shows real-time measurements such as voltage, current, active power, reactive power, power factor, frequency, and total energy (kWh).
  • "SET" Button: Used to enter the parameter setting mode or confirm selections.
  • Arrow Buttons (Left, Right, Up, Down): Used to navigate through different display screens or adjust parameter values in setting mode.

6.2 Reading Energy Data

Press the arrow buttons to cycle through the various measurement screens. Common readings include:

  • Énergie active totale (kWh)
  • Énergie active directe (kWh)
  • Énergie active inverse (kWh)
  • Voltage (V) per phase
  • Courant (A) par phase
  • Puissance active (kW) par phase et totale
  • Reactive Power (kVar) per phase and total
  • Facteur de puissance (PF)
  • Fréquence (Hz)

6.3 Communications RS485

The meter supports RS485 communication with MODBUS-RTU protocol. This allows for remote reading of meter data and configuration. Refer to the MODBUS communication protocol document for detailed register addresses and commands.

7. Entretien

The DTSD1352 energy meter is designed for long-term, reliable operation with minimal maintenance. However, periodic checks are recommended.

  • Nettoyage: Veillez à ce que le compteur reste propre et exempt de poussière. Utilisez un chiffon doux et sec pour le nettoyer. N'utilisez pas de produits abrasifs ni de solvants.
  • Relations: Periodically check all wiring connections to ensure they are tight and secure. Loose connections can lead to inaccurate readings or overheating.
  • Environnement: Veillez à ce que l'environnement de travail reste dans les plages de température et d'humidité spécifiées.
  • Étalonnage: The meter is factory calibrated. If you suspect inaccuracies, contact qualified service personnel for recalibration.

8. Dépannage

This section provides solutions to common issues you might encounter with the DTSD1352 meter.

Tableau 8.1 : Guide de dépannage
ProblèmeCause possibleSolution
L'écran du compteur est vide.Le compteur n'est pas alimenté.Check the main power supply and wiring connections to the meter's voltage input terminals. Ensure fuses are intact.
Relevés énergétiques inexacts.Incorrect wiring, incorrect CT ratio setting (if applicable), faulty CTs, or meter malfunction.Verify all wiring connections according to Section 5. Ensure CT polarity is correct. Check if the CT ratio programmed in the meter matches the physical CTs. If issues persist, contact technical support.
Panne de communication RS485.Incorrect wiring of RS485 terminals (A/B), incorrect communication parameters (baud rate, parity, address), or software issue.Check RS485 A and B terminal connections. Verify communication settings (baud rate, data bits, stop bits, parity, meter address) in your master device match the meter's settings. Ensure proper termination resistors are used if necessary.
Meter shows "Error" or specific error codes.Défaut interne ou problème opérationnel spécifique.Note down the error code and consult the full product manual or contact technical support for specific error code interpretations and solutions.

9. Garantie et assistance

This product is manufactured by TGLGTQPX and sold under the Acrel brand. For specific warranty terms and conditions, please refer to the documentation provided at the time of purchase or contact your vendor. General support for the Acrel DTSD1352 meter can be obtained through the manufacturer's official channels or your authorized distributor.

For technical assistance, troubleshooting beyond this manual, or spare parts, please contact:

  • Fabricant: TGLGTQPX
  • Marque du produit : Acrel
  • Modèle: DTSD1352
  • (Informations de contact telles que website or email would typically be provided here by the manufacturer.)

Documents connexes - DTSD1352

Préview Manuel d'installation et d'utilisation du compteur électrique monophasé ADL100-ET
Guide complet d'installation et d'utilisation du compteur électrique monophasé Acrel ADL100-ET. Ce manuel détaille les spécifications techniques, les descriptions fonctionnelles, les instructions de câblage, les menus d'affichage, les procédures de programmation et les protocoles de communication (Modbus RTU).
Préview Acrel ADL3000 Smart Meter: Installation and Operation Manual
Comprehensive guide for the Acrel ADL3000 smart meter, covering installation, operation, technical specifications, and display functions for industrial and utility power monitoring.
Préview Acrel ADL400 Three Phase Electric Meter: Installation and Operation
Detailed information on the Acrel ADL400 three-phase electric meter, covering its general features, functions, electrical parameters, working environment, installation, and wiring diagrams for low-voltage energy measurement.
Préview Acrel D318 Harmonic Meter Operation Instruction Manual
Operation instruction manual for the Acrel D318 External Roche Coil and Switched Transformer Harmonic Meter. Details features, technical specifications, and connection methods for energy saving and power monitoring applications.
Préview Compteur intelligent Acrel ADL3000-E : Manuel d’installation et d’utilisation
Instructions complètes d'installation et d'utilisation du compteur intelligent Acrel ADL3000-E, couvrant les spécifications techniques, le câblage, les fonctions d'affichage et les protocoles de communication.
Préview Manuel d'installation et d'utilisation du wattmètre CC monté sur rail DJSF1352-RN
This document provides comprehensive installation and operation instructions for the Acrel DJSF1352-RN rail-mounted DC power meter. It covers product specifications, technical parameters, wiring diagrams, operational guidance, menu settings, and communication protocols (Modbus-RTU, DLT645-07).