Manuel d'utilisation de l'unité de récupération de réfrigérant Value VRR24M-C

Model: VRR24M-C

Brand: Value

Produit terminéview

The Value VRR24M-C is a compact and efficient refrigerant recovery unit designed for professional use. It is suitable for recovering various types of refrigerants, including R12, R134a, R407c, R22, R410a, R32, and R1234yf, among others. Its robust design and user-friendly features make it an essential tool for HVAC/R technicians.

Value VRR24M-C Refrigerant Recovery Unit, front-side view

Image: The Value VRR24M-C Refrigerant Recovery Unit, showcasing its compact design, control panel with gauges, and connection ports. The unit features a sturdy handle for portability and a ventilation grille on the side.

Caractéristiques principales :

Consignes de sécurité

Always read and understand all safety warnings and instructions before operating the VRR24M-C unit. Failure to do so may result in serious injury or equipment damage.

Installation

  1. Déballage: Carefully remove the VRR24M-C unit from its packaging. Inspect for any shipping damage.
  2. Placement: Place the unit on a stable, level surface in a well-ventilated area, away from direct sunlight or heat sources.
  3. Connexion électrique : Connect the power cord to a grounded 230V/50Hz electrical outlet. Ensure the power switch on the unit is in the "OFF" position before connecting.
  4. Connexions de tuyau :
    • Connect the appropriate hoses from the system to be recovered to the "IN" port of the recovery unit.
    • Connect a hose from the "OUT" port of the recovery unit to the recovery cylinder.
    • Assurez-vous que toutes les connexions sont bien serrées pour éviter les fuites.
  5. Cylinder Preparation: Ensure the recovery cylinder is empty and has sufficient capacity for the refrigerant being recovered. Weigh the cylinder before and during recovery to prevent overfilling.

Mode d'emploi

The VRR24M-C unit offers different recovery modes for optimal performance.

Étapes générales de l'opération :

  1. Ensure all hoses are correctly connected and valves are in the appropriate positions (refer to your system's specific recovery procedure).
  2. Mettez l'interrupteur principal sur la position « MARCHE ».
  3. Select the desired recovery mode using the operation knob (e.g., Gas, Liquid, Push/Pull).
  4. Monitor the high and low-pressure gauges during the recovery process.
  5. The unit will automatically shut off if the pressure exceeds 38.5 bar (558 psi).
  6. Once recovery is complete, or the system pressure reaches the desired vacuum level, turn off the unit and close all valves.
  7. Débranchez les tuyaux avec précaution, en faisant attention à toute pression résiduelle.

Recovery Efficiency (Approximate):

Refrigerant CategoryModeEfficiency (kg/min)
Category III (e.g., R12, R134a, R401c, R406a, R500, R1234yf)Gaz2.6
Liquid / Push / Pull7.50
Category IV (e.g., R22, R401a, R401b, R402b, R407c, R407d, R408a, R409a, R502, R509)Gaz2.9
Liquid / Push / Pull8.50
Category V (e.g., R402a, R404a, R407a, R407b, R410a, R507, R32)Gaz3.9
Liquid / Push / Pull9.50

Note: Recovery efficiency may vary based on ambient temperature, system conditions, and refrigerant type.

Entretien

Regular maintenance ensures the longevity and optimal performance of your VRR24M-C unit.

Dépannage

Cette section propose des solutions aux problèmes opérationnels courants. Pour tout problème non répertorié ici, veuillez contacter un technicien qualifié.

ProblèmeCause/solution possible
L'unité ne s'allume pas.
  • Vérifiez que le cordon d'alimentation est bien branché dans une prise de courant fonctionnelle.
  • Vérifiez que l'interrupteur d'alimentation est en position « MARCHE ».
  • Vérifiez le disjoncteur ou le fusible de la prise de courant.
Lenteur du rétablissement.
  • Ensure hoses are properly connected and not kinked.
  • Check for blockages in hoses or filters.
  • Verify the correct recovery mode (Gas/Liquid) is selected for the refrigerant state.
  • Ambient temperature may be too low (operating temperature 0-40°C).
Unit shuts down automatically.
  • High-pressure shutdown: The pressure may have exceeded 38.5 bar (558 psi). Check for overfilled recovery cylinder or blockages.
  • Overheating: Ensure adequate ventilation around the unit. Allow the unit to cool down.
Fuites de réfrigérant détectées.
  • Tighten all hose connections and fittings.
  • Vérifiez l'état des tuyaux et remplacez-les si nécessaire.
  • Check O-rings and seals on connections.

Caractéristiques

ParamètreValeur
Modèle de produitVRR24M-C
Réfrigérants compatiblesCategory III: R12, R134a, R401c, R406a, R500, R1234yf
Category IV: R22, R401a, R401b, R402b, R407c, R407d, R408a, R409a, R502, R509
Category V: R402a, R404a, R407a, R407b, R410a, R507, R32
Alimentation électrique230V / 50Hz
Puissance du moteur1 CV
Vitesse du moteur3000 tr/min
Courant maximal5 A
Type de compresseurPiston compressor, air-cooled, oil-free, maintenance-free
Automatic Shutdown Pressure38.5 bar / 3850 kPa (558 psi)
Température de fonctionnement0 - 40 °C
Dimensions (L x l x H)370 x 250 x 300 mm
Poids11.5 kg
Appareils compatiblesRefrigerator, Air Conditioner, Cooling Unit

Garantie et assistance

Specific warranty details are not provided in the product information. Please refer to your purchase documentation or contact the retailer/manufacturer for warranty terms and conditions.

For technical support or service inquiries, please contact Value customer service or your authorized dealer.

Documents connexes - VRR24M-C

Préview VALUE VRR24M-C Recovery Unit User Manual
User manual for the VALUE VRR24M-C Refrigerant Recovery Unit, detailing general safety, operation, specifications, parts, wiring, and troubleshooting.
Préview VALUE VRR12L-R32 / VRR24L-R32 Recovery Unit Manual
This manual provides operating instructions, safety guidelines, and troubleshooting tips for the VALUE VRR12L-R32 and VRR24L-R32 Recovery Units. It covers essential information for safe and efficient refrigerant recovery.
Préview Manuel d'utilisation et informations techniques de la pompe à vide à variateur VALUE VRP-15DN
Guide complet de la pompe à vide à variateur VALUE VRP-15DN, comprenant les spécifications techniques, les applications, les précautions de sécurité, le mode d'emploi, les procédures de maintenance, un guide de dépannage et une liste de pièces détachées. Conçue pour les systèmes CVC et les réfrigérants tels que l'ammoniac, le R-32 et le R-1234yf.
Préview Manuel d'utilisation de l'outil d'évasement de batterie Li-VET-19Li VALUE VET-19Li
Manuel d'utilisation de l'outil d'évasement de batterie Li-VET-19Li VALUE, fournissant des consignes de sécurité, des spécifications techniques, des instructions d'utilisation, des procédures de charge et de dépannage.
Préview VALUE VTE Series Power Tube Expander User Manual - Operation and Specifications
User manual for the VALUE VTE Series Power Tube Expander (models VTE-29D, VTE-42D). Includes instructions on charging, oil changes, lubrication, safety, operation, pressure relief, and technical specifications.
Préview VALUE VRR24M-C Refrigerant Recovery Unit - Product Overview & Caractéristiques
Détaillé surview and specifications for the VALUE VRR24M-C Refrigerant Recovery Unit, featuring a DC brushless motor, oil-free compressor, and suitability for R32 refrigerant. This unit offers fast recovery, better visibility, and a self-purge function.