PUSR USR-DR302

Manuel d'utilisation du convertisseur Modbus RS485 vers Ethernet sur rail DIN PUSR USR-DR302

Model: USR-DR302

Introduction

The PUSR USR-DR302 is a DIN-Rail mounted Modbus RS485 to Ethernet converter designed for bidirectional transparent data transmission between RS485 serial devices and an Ethernet network. This device facilitates communication by converting serial data to TCP/IP data packets, enabling seamless integration of serial devices into modern network infrastructures. Its compact design and DIN-rail mounting capability make it suitable for industrial applications with limited space.

Key features include industrial-grade RS485 port, Modbus RTU to Modbus TCP conversion, virtual serial software support, network heartbeat packet functionality, and robust PC+ABSC material construction for safety and durability.

Produit terminéview

Devant view of the PUSR USR-DR302 DIN-Rail Modbus RS485 to Ethernet Converter

Figure 1 : Devant view of the USR-DR302 converter, showing the Reload button, PWR, WORK, RX, and TX indicator LEDs, and the USR-DR302 branding. The top features screw terminals for LAN and GBA connections, while the bottom has terminals for DC 5-36V power input.

Diagram illustrating bidirectional data flow between RS485 and Ethernet via the USR-DR302 converter

Figure 2 : Conceptual diagram showing the USR-DR302 converter facilitating bidirectional data transmission between an RS485 network (red line) and an Ethernet network (blue line).

Dimensions and port details of the USR-DR302 converter

Figure 3 : Détaillé view of the USR-DR302 showing its dimensions (109.66mm height, 64.67mm width, 28mm depth) and close-ups of the RJ45 Ethernet port and screw terminals.

Diagram showing Modbus TCP to Modbus RTU conversion using USR-DR302

Figure 4 : Illustration of the USR-DR302 converting Modbus TCP from configuration software to Modbus RTU for communication with a PLC (Programmable Logic Controller).

Installation

This section outlines the steps for physically installing and initially configuring the USR-DR302 converter.

1. Installation physique

  1. Montage: The USR-DR302 is designed for DIN-rail mounting. Securely attach the device to a standard DIN rail in your control cabinet or enclosure.
  2. Connexion électrique : Connect a DC 5-36V power supply to the designated power terminals on the device. Ensure correct polarity.
  3. Connexion RS485 : Connect your RS485 serial device(s) to the RS485 terminals (A, B, G) on the converter. Observe proper wiring for RS485 differential signals.
  4. Connexion Ethernet : Connect an Ethernet cable from your network switch or router to the RJ45 Ethernet port on the USR-DR302.

2. Configuration initiale

Configuration of the USR-DR302 is typically performed via a web interface or dedicated software provided by the manufacturer. Refer to the manufacturer's official documentation for detailed instructions on accessing and using the configuration tools.

  • Paramètres réseau : Configure the IP address, subnet mask, and gateway for the converter to integrate it into your Ethernet network.
  • Paramètres du port série : Set the baud rate, data bits, stop bits, and parity to match your RS485 serial device(s).
  • Mode de fonctionnement: Select the desired operating mode (e.g., TCP Client, TCP Server, UDP Client, HTTP Client) based on your application requirements.

Modes de fonctionnement

The USR-DR302 supports several operating modes to accommodate various network communication scenarios.

Mode client TCP

Diagram illustrating TCP Client mode operation of USR-DR302

Figure 5 : Representation of the USR-DR302 in TCP Client mode, initiating a connection to a TCP Server (PC) and facilitating serial communication with a connected serial device.

In TCP Client mode, the USR-DR302 initiates a TCP connection to a user-configured destination IP address and port. If the connection fails, the converter will continuously attempt to reconnect. Data from the connected serial device is then transmitted over this established TCP connection to the server.

Mode serveur TCP

When configured as a TCP Server, the USR-DR302 monitors a defined port and waits for incoming TCP client connections. Once a client successfully connects, data received from the serial device is transmitted to all connected TCP clients. This mode is suitable for applications where multiple network devices need to access a single serial device.

Mode client UDP

Diagram illustrating UDP Client mode operation of USR-DR302

Figure 6 : Illustration of the USR-DR302 in UDP Client mode, communicating with specific target IP addresses and ports, ensuring data transmission accuracy. It also shows automatic data transmission to the last device after receiving data.

In UDP Client mode, the USR-DR302 communicates exclusively with the target interface of a specified IP address, which helps ensure data transmission accuracy. The DR302 can also automatically transmit data to the last device it communicated with after receiving new data, making it suitable for scenarios involving multiple network devices communicating with the converter.

Mode client HTTP

The USR-DR302 supports transmitting serial data to a specified server using HTTP (GET/POST) requests. This mode is useful for integrating serial device data into web-based applications or cloud platforms.

Entretien

To ensure the longevity and reliable operation of your USR-DR302 converter, follow these general maintenance guidelines:

  • Conditions environnementales : Operate the device within its specified temperature and humidity ranges. Avoid exposure to extreme conditions, direct sunlight, or excessive dust.
  • Nettoyage: Periodically clean the exterior of the device with a soft, dry cloth. Do not use liquid cleaners or solvents. Ensure the device is powered off before cleaning.
  • Mises à jour du micrologiciel : Vérifiez le fabricant website for any available firmware updates. Applying updates can improve performance, add features, or resolve known issues. Follow the manufacturer's instructions carefully when performing firmware updates.
  • Intégrité de la connexion : Regularly inspect all cable connections (power, RS485, Ethernet) to ensure they are secure and free from damage. Loose connections can lead to intermittent operation.

Dépannage

This section provides solutions to common issues you might encounter with the USR-DR302 converter.

ProblèmeCause possibleSolution
No Power Indicator (PWR LED off)Pas d'alimentation, volume incorrecttage, or faulty power connection.Verify the power supply is connected and providing DC 5-36V. Check power cable and terminals for secure connection and correct polarity.
Aucune connectivité réseauIncorrect Ethernet cable connection, network configuration issues (IP address, subnet), or network device problems.Ensure the Ethernet cable is securely connected. Check network settings (IP, subnet, gateway) in the converter's configuration. Verify the network switch/router is functioning correctly.
Échec de la communication RS485Incorrect RS485 wiring, mismatched serial port settings (baud rate, parity), or faulty serial device.Check RS485 wiring (A to A, B to B). Confirm serial port settings on the converter match the connected serial device. Test the serial device independently if possible.
Data Transmission Issues (Intermittent or No Data)Incorrect operating mode configuration, network congestion, or software issues on the host PC/server.Verify the selected operating mode (TCP Client/Server, UDP Client, HTTP Client) is appropriate for your application and correctly configured. Check network traffic and ensure host software is properly configured to receive data.
Device Unresponsive (Reload button)Software hang or configuration error.Press and hold the 'Reload' button for a few seconds to reset the device to factory defaults (refer to manufacturer's guide for exact procedure and implications). Power cycle the device.

Caractéristiques

FonctionnalitéDétail
ModèleUSR-DR302
MarquePUSR
Dimensions du produit (L x l x H)8.46 x 6.3 x 1.97 pouces (21.49 x 16.00 x 5.00 cm)
Poids de l'article8.4 onces (238 grammes)
Puissance d'entréeDC 5-36V
Interface sérieRS485
Interfaces réseauEthernet RJ45
Modes de fonctionnementTCP Client, TCP Server, UDP Client, HTTP Client
MatérielPC + ABSC (Flame Retardant V0)
ProtectionLevel 4 Anti-static, Level 3 Electrical Pulse, Level 2 Surge
MontageDIN-Rail

Demande Examples

The USR-DR302 converter is suitable for various industrial and commercial applications requiring serial to Ethernet communication.

USR-DR302 in a power data network transmission application

Figure 7 : The USR-DR302 integrated into a power data network transmission system, converting terminal data from distribution boxes into network data for real-time communication.

USR-DR302 used in a barrier gate control system

Figure 8 : Un example of the USR-DR302 being used in a barrier gate control system, likely for remote monitoring or control of the gate via Ethernet.

USR-DR302 connecting multiple signal lights to an Ethernet network

Figure 9 : Depiction of multiple USR-DR302 devices connecting various signal lights to a central server via an Ethernet network, enabling centralized control and monitoring.

Garantie et assistance

Information regarding product warranty, technical support, and service centers is typically provided by the manufacturer or your point of purchase. Please refer to the documentation included with your product or visit the official PUSR website pour obtenir les informations les plus récentes et détaillées.

For further assistance, you may contact PUSR customer support through their official channels.

Documents connexes - USR-DR302

Préview Manuel du routeur industriel 4G USR-G806p
Ce manuel présente l'USR-G806p, un routeur industriel 4G, de manière complète. Il couvre les caractéristiques du produit, les interfaces matérielles, les instructions d'utilisation, les fonctions réseau, les capacités VPN, les paramètres de pare-feu, les fonctions de serveur de port série et la gestion du système. Conçu pour les environnements industriels difficiles, l'USR-G806p offre des performances et une connectivité robustes.
Préview Manuel d'utilisation du routeur LTE industriel USR-G806s-G - PUSR
Manuel d'utilisation complet du routeur industriel 4G LTE PUSR USR-G806s-G. Ce manuel détaille les caractéristiques, les spécifications, la configuration et les fonctions avancées pour les applications M2M et IoT, notamment les capacités GPS et DTU.
Préview Mini-ordinateur industriel USR-EG628 : Caractéristiques, spécifications et guide de commande | Pusr
Découvrez le Pusr USR-EG628, un mini-ordinateur industriel équipé d'un processeur ARM à 4 cœurs, de Linux Ubuntu et de Node-RED. Explorez ses fonctionnalités, ses caractéristiques matérielles et logicielles, ainsi que les options de commande pour l'informatique de périphérie et l'automatisation.
Préview PUSR USR-S100 PV Data Stick: Industrial IoT WiFi to RS485 Converter Specification
Detailed technical specifications for the PUSR USR-S100 PV Data Stick, a cost-effective WiFi communication product for photovoltaic networking, enabling RS-485 communication with industrial IoT devices.
Préview Catalogue de la série de routeurs industriels PUSR - Solutions IoT 4G et 5G
Découvrez le catalogue complet de routeurs industriels PUSR, incluant des modèles 4G LTE et 5G hautes performances. Explorez les spécifications détaillées, les informations de commande, les schémas d'application et les cas d'utilisation typiques de modèles tels que les USR-G809, USR-G808, USR-G806s, USR-G781, USR-G806, USR-G805 et USR-G810. Découvrez les services cloud PUSR pour une gestion IoT efficace.
Préview USR-TCP232-30X 系列工业级单串口服务器说明书
USR-TCP232-30X 系列工业级单串口服务器,提供 RS232/RS485/RS422 串口与 RJ45 网口之间的高速双向数据传输。支持 Modbus 网关、边缘计算、MQTT 等多种功能,专为工业物联网场景设计,确保稳定可靠的 7x24H 运行。