Introduction
This manual provides essential information for the proper installation, operation, and maintenance of the Gentex GCS24CR Fire Evacuation Strobe. Please read these instructions thoroughly before installation and retain for future reference.
The Gentex GCS24CR is a ceiling mount strobe designed for fire evacuation systems. It offers dependable visual alarms with selectable candela options and minimal operating current.

Image 1: Gentex GCS24CR Fire Evacuation Strobe. This image shows the red faceplate and the ceiling mount design of the strobe unit.
Informations importantes sur la sécurité
AVERTISSEMENT:
- L'installation doit être effectuée par un personnel qualifié, conformément à tous les codes et normes électriques locaux et nationaux.
- Disconnect power before installing, servicing, or removing the device. Failure to do so may result in electric shock or equipment damage.
- This device is intended for use with fire alarm control panels (FACP) that provide regulated 24VDC power.
- Do not paint over the strobe lens as this will impair its effectiveness.
Configuration et installation
1. Déballage
Carefully remove the GCS24CR strobe from its packaging. Inspect the unit for any signs of damage. If damage is found, do not install and contact your supplier.
2. Montage
The GCS24CR is designed for ceiling mount applications. It utilizes a 4-inch mounting plate, which incorporates the SuperSlide feature for easy installation and supervision testing.
- Secure the mounting plate to a standard 4-inch square or octagonal electrical box. Ensure the plate is firmly attached.
- Connect the wiring from the Fire Alarm Control Panel (FACP) to the terminal block on the strobe unit. Observe proper polarity.
- Slide the strobe unit onto the mounting plate, ensuring it locks securely into place. The SuperSlide feature allows for easy alignment.
3. Candela Selection
The GCS24CR offers field-selectable candela options. These settings determine the light output intensity of the strobe. The available options are 15, 30, 75, 95, 115, and 150 candela.
- Locate the candela selection switches on the back of the strobe unit.
- Using a small screwdriver or similar tool, set the switches according to the desired candela rating as specified by local codes and system design.
- Refer to the product label or technical documentation for the exact switch configurations for each candela setting.
Opération
The Gentex GCS24CR operates as a visual alarm device within a fire evacuation system. When activated by a compatible Fire Alarm Control Panel (FACP), the strobe will flash at a minimum rate of 1Hz, providing a visual alert.
- Activation : The strobe activates upon receiving a 24VDC signal from the FACP.
- Taux de flash : The strobe maintains a minimum flash rate of 1Hz, regardless of input voltage fluctuations, ensuring consistent visual signaling.
- Tirage actuel : The device is designed for minimal operating current, optimizing system power requirements.
For systems requiring synchronized strobes, ensure the FACP or a compatible synchronization module is used. The GCS24CR is designed to synchronize with other Gentex strobes when connected to a compatible synchronization source.
Entretien
The Gentex GCS24CR requires minimal maintenance to ensure proper operation. Regular inspections are recommended.
- Nettoyage: Periodically clean the strobe lens with a soft, damp cloth to remove dust or debris. Do not use abrasive cleaners.
- Inspection visuelle : Annually inspect the unit for any physical damage, discoloration, or loose connections.
- Tests fonctionnels : Conduct functional tests as required by local codes and standards (e.g., NFPA 72). This typically involves activating the fire alarm system to verify the strobe flashes correctly.
PRUDENCE:
Do not attempt to repair the unit. Refer all servicing to qualified personnel. Unauthorized repairs will void the warranty.
Dépannage
If the Gentex GCS24CR strobe is not functioning as expected, refer to the following troubleshooting guide:
| Problème | Cause possible | Solution |
|---|---|---|
| Strobe does not flash. | No power from FACP. Câblage incorrect. Appareil défectueux. | Verify 24VDC power at the terminal block. Check wiring for correct polarity and secure connections. Replace the unit if power and wiring are confirmed correct. |
| Strobe flashes inconsistently. | Puissance insuffisante. Problème de câblage. Incompatible synchronization. | Ensure stable 24VDC power supply. Check for loose or damaged wiring. Verify FACP or synchronization module compatibility and proper connection. |
| Strobe lens is dirty or obstructed. | Poussière ou débris accumulés. | Nettoyez la lentille avec un chiffon doux.amp cloth. Ensure no obstructions are blocking the light path. |
If troubleshooting steps do not resolve the issue, contact Gentex technical support or a qualified fire alarm technician.
Caractéristiques
| Fonctionnalité | Détail |
|---|---|
| Numéro de modèle | GCS24-CR |
| Marque | Gentex |
| Vol d'entréetage | 24VDC (Nominal) |
| Paramètres de la bougie | 15, 30, 75, 95, 115, 150 cd (selectable) |
| Taux de flash | Minimum 1Hz |
| Type de montage | Montage au plafond |
| Couleur | Façade rouge |
| Matériel | Metal (housing), Plastic (lens) |
| Type de source lumineuse | Xénon |
| Poids de l'article | 1.06 livres (environ) |
| Code UPC | 700217018453 |
Informations sur la garantie
Gentex products are warranted to be free from defects in materials and workmanship under normal use and service for a period specified in the product's official warranty statement. For complete warranty details, please refer to the official documentation provided with your product or visit the Gentex website.
This warranty does not cover damage caused by improper installation, misuse, abuse, unauthorized repairs, or acts of nature.
Assistance technique et contact
For technical assistance, product inquiries, or to report issues, please contact Gentex customer support.
Société Gentex
www.gentex.com
Please have your product model number (GCS24-CR) and serial number (if applicable) ready when contacting support.





