1. Introduction

This manual provides detailed instructions for the installation, operation, and maintenance of the Watts 009M2 Reduced Pressure Zone (RPZ) Backflow Preventer. This device is designed to protect potable water supplies from contamination due to backpressure or backsiphonage from non-potable sources. It is crucial to read and understand all instructions before installation and use to ensure proper function and safety.

The Watts 009M2 RPZ assembly features a compact, modular design for easy maintenance, with a single access cover for in-line repairs. It is suitable for continuous pressure piping applications and cross-connections identified as health hazards.

2. Informations importantes sur la sécurité

3. Produit terminéview et composants

The Watts 009M2 Reduced Pressure Zone Backflow Preventer is constructed with a durable bronze body and features NPT end connections. Key components include:

Watts 009M2 Reduced Pressure Zone Backflow Preventer
Figure 1: Watts 009M2 Reduced Pressure Zone Backflow Preventer. This image shows the bronze body, quarter-turn shutoff valves with green handles, and multiple test cocks on top.

4. Configuration et installation

  1. Vérification avant l'installation :
    • Verify that the product model (009M2) and size (2 inch) match your requirements.
    • Vérifiez que l'appareil n'a pas subi de dommages liés au transport.
    • Ensure all necessary tools and materials for installation are available.
  2. Préparation du site :
    • Choose an installation location that allows for easy access for testing and maintenance.
    • Ensure adequate drainage for the relief valve discharge.
    • The device should be installed horizontally, with the relief valve pointing downwards.
  3. Connexion de tuyauterie :
    • Flush the upstream piping thoroughly to remove any debris before connecting the backflow preventer.
    • Connect the inlet and outlet piping to the NPT connections on the device. Use appropriate thread sealant.
    • Avoid overtightening connections to prevent damage to the bronze body.
    • Ensure the flow arrow on the device body matches the direction of water flow.
  4. Relief Valve Drain:
    • Connect a drain line to the relief valve outlet. The drain line must be adequately sized and sloped to allow for free discharge and prevent backpressure on the relief valve.
    • Ensure the drain line terminates in an air gap, preventing any possibility of cross-connection.
  5. Vérification après l'installation :
    • Slowly open the upstream shutoff valve, then the downstream shutoff valve, to gradually fill the system and prevent water hammer.
    • Inspectez toutes les connexions pour les fuites.
    • Perform initial testing by a certified backflow prevention tester to ensure proper operation and compliance with local codes.

5. Mode d'emploi

The Watts 009M2 is designed for continuous pressure operation. Normal operation involves the device being fully open, allowing water to flow through the system while providing backflow protection.

6. Entretien

Regular maintenance is critical for the reliable performance of your backflow preventer. The modular design and single access cover simplify servicing.

7. Dépannage

ProblèmeCause possibleSolution
Water discharge from relief valve (continuous)
  • Fouled first check valve
  • Damaged relief valve seat or disc
  • Excessive backpressure
  • Clean or repair first check valve.
  • Inspect and replace relief valve components.
  • Identify and correct source of backpressure.
Débit d'eau nul ou réduit
  • Shutoff valves closed
  • Debris obstructing flow
  • Fouled check valves
  • Assurez-vous que les vannes d'arrêt sont complètement ouvertes.
  • Isolate and inspect for debris.
  • Clean or repair check valves.
Fuites provenant des connexions
  • Filetages mal étanches
  • Joints endommagés
  • Re-apply thread sealant and tighten connections.
  • Inspect and replace gaskets.

For issues not listed or if troubleshooting steps do not resolve the problem, contact a certified plumbing professional or Watts technical support.

8. Spécifications

Numéro de modèle0063010 (009M2)
Backflow Preventer TypeAssemblage de zone de pression réduite
Matériau du corpsBronze
Taille du raccord d'entrée/sortie2 pouces (50 mm)
Type de connexion entrée/sortieFemale Threaded NPT
Pression de service maximale175 PSI (12.10 BAR)
Température maximale180°F (82°C)
Température minimale33°F (0.5°C)
Type de protectionBackpressure and Backsiphonage
Dimensions du produit (L x l x H)22 x 10 x 8 pouces
Poids de l'article27 livres
Lead Free StatusNO (For non-potable use only)

9. Garantie et assistance

Specific warranty information for Watts products is typically provided with the product packaging or available on the official Watts website. Please refer to these resources for the most current warranty terms and conditions.

For technical support, replacement parts, or further assistance, please contact Watts customer service or visit their official website. Ensure you have your product model number (0063010) and serial number (if applicable) ready when contacting support.

Watts Officiel Website: www.watts.com

Documents connexes - 0063010

Préview Spécifications techniques de l'assemblage de la zone de pression réduite de la série Watts LF909
Spécifications techniques complètes du dispositif anti-retour Watts série LF909 (21/2" - 10"). Caractéristiques, fonctionnement, matériaux, dimensions et capacité de ce dispositif sans plomb avec capteur d'inondation intégré.
Préview Série Watts 009, LF009, LFU009, SS009, U009 : Manuel d’installation, d’entretien et de réparation
Ce manuel complet de Watts fournit des instructions essentielles pour l'installation, la maintenance et la réparation des dispositifs anti-retour des séries 009, LF009, LFU009, SS009 et U009. Il détaille les consignes de sécurité, les procédures d'installation, l'inspection, l'entretien, le dépannage et les informations relatives à la garantie de ces dispositifs anti-retour indispensables.
Préview Watts Series LF909, 909RPDA Reduced Pressure Zone Assembly Installation, Maintenance, and Repair Manual
Comprehensive guide for installing, maintaining, and repairing Watts Series LF909 and 909RPDA Reduced Pressure Zone Assemblies and Reduced Pressure Detector Assemblies. Covers safety, installation guidelines, testing procedures, servicing, troubleshooting, and sensor connection kits.
Préview Manuel d'installation, d'entretien et de réparation des ensembles de zones à pression réduite Watts séries 909, LF909 et 909RPDA
Comprehensive guide for the installation, maintenance, and repair of Watts Series 909, LF909, and 909RPDA Reduced Pressure Zone Assemblies, including safety warnings, installation guidelines, testing procedures, servicing instructions, troubleshooting, and warranty information.
Préview Manuel d'installation, d'entretien et de réparation des ensembles de zones à pression réduite Watts séries 009, LF009, LFU009, SS009 et U009
Comprehensive guide for the installation, maintenance, and repair of Watts Series 009, LF009, LFU009, SS009, and U009 Reduced Pressure Zone Assemblies. Covers safety, installation guidelines, annual inspection, servicing procedures, troubleshooting, and sensor connection kits.
Préview Ensembles de zones à pression réduite Watts série LF909 - Spécifications techniques
Spécifications techniques détaillées des groupes de zones à pression réduite Watts série LF909 : caractéristiques, fonctionnement, dimensions, poids et capacité. Conçus pour la protection contre les interconnexions d’eau potable.