1. Introduction
This manual provides detailed instructions for the installation, operation, and maintenance of the Sure-Lites All-Pro APC7RG Combination LED Exit Sign and Emergency Light. This unit is designed to meet code requirements for emergency egress lighting in commercial buildings, offering both an illuminated exit sign and emergency lighting with adjustable LED heads.

Image 1.1 : Terminéview of the Sure-Lites All-Pro APC7RG Combination LED Exit Sign and Emergency Light units.
2. Consignes de sécurité
Please read and understand all instructions before installation and operation. Retain this manual for future reference.
- Sécurité électrique : All wiring must be performed by a qualified electrician in accordance with national and local electrical codes. Ensure power is disconnected at the circuit breaker before installation or servicing.
- Intégrité du produit : Do not modify or alter the product. Use only manufacturer-specified replacement parts.
- Emplacement: This unit is UL certified and damp location listed. Ensure the installation environment is suitable.
- Batterie: The unit contains a nickel-cadmium battery. Dispose of batteries according to local regulations.
3. Contenu du colis
Vérifiez que tous les composants sont présents avant de commencer l'installation :
- Sure-Lites All-Pro APC7RG Combination LED Exit Sign and Emergency Light Unit
- Snap-fit canopy with captive mounting screws
- Directional chevrons (snap-in/snap-out)
- Installation hardware (screws, wire nuts)
- Nickel Cadmium Battery (pre-installed or separate)
4. Configuration et installation
The APC7RG is designed for easy installation with universal J-box mounting and snap-fit construction, allowing for installation in under 5 minutes.
4.1 options de montage
The unit offers universal surface mounting flexibility and can be configured for:
- Montage au plafond
- Support mural
- End mount
It supports configurable single or double faces.

Image 4.1: Key installation and performance features.
4.2 Câblage
- Assurez-vous que le courant est coupé au niveau du disjoncteur.
- Connect the unit's wiring to the building's AC power supply (120V) according to local electrical codes.
- Secure the unit to the universal J-box using the provided hardware and snap-fit canopy.
4.3 Field Selectable Features
The APC7RG exit face is illuminated with long-lasting LEDs that are field selectable for red or green letters. The unit is pre-set to red letters and can be easily changed to green letters during installation. Snap-in/snap-out directional chevrons (arrows) can also be configured to indicate the direction of egress.

Image 4.2 : Vue éclatée view highlighting field-selectable features and components.

Image 4.3 : Example of selectable red or green exit sign faces in commercial environments.
5. Mode d'emploi
5.1 Fonctionnement normal
When AC power is supplied, the LED exit sign will illuminate, and the battery will charge. A power indicator light (usually green) located on the bottom of the exit sign will confirm AC power is present and the battery is charging.
5.2 Fonctionnement d'urgence
In the event of an AC power failure, the unit will automatically switch to battery backup mode. The exit sign and emergency lights will operate for a minimum of 90 minutes, providing up to 17 feet of emergency egress coverage.
5.3 Tests
A test switch is located on the bottom of the exit sign. Press and hold the test switch to simulate a power outage. The unit should switch to battery power, and the exit sign and emergency lights should illuminate. Release the switch to return to normal operation. Regular testing is recommended to ensure proper functionality.
6. Entretien
- Batterie: The nickel-cadmium battery is designed for no maintenance. However, it is recommended to perform monthly 30-second functional tests and annual 90-minute discharge tests to ensure the battery holds a charge and the unit operates correctly during an emergency.
- Nettoyage: Nettoyez l'extérieur de l'appareil avec un chiffon doux.amp chiffon. N'utilisez pas de nettoyants abrasifs ou de solvants.
- Inspection: Periodically inspect the unit for any physical damage or discoloration.
7. Dépannage
Consultez le tableau ci-dessous pour connaître les problèmes courants et leurs solutions.
| Problème | Cause possible | Solution |
|---|---|---|
| Exit sign or emergency lights do not illuminate during power outage. | Battery not charged or faulty; unit not connected to AC power. | Ensure AC power is connected and indicator light is on. Allow 24 hours for initial battery charge. If problem persists, battery may need replacement. |
| Le voyant d’alimentation est éteint. | No AC power; faulty wiring; indicator light malfunction. | Check circuit breaker. Verify wiring connections. Contact a qualified electrician if necessary. |
| Emergency lights do not stay on for 90 minutes during test. | Capacité de la batterie réduite. | Perform a full 90-minute discharge test and recharge. If run time is still insufficient, the battery may need replacement. |
8. Spécifications
Key technical details for the Sure-Lites All-Pro APC7RG unit:

Image 8.1 : Dimensions et certifications du produit.
| Fonctionnalité | Détail |
|---|---|
| Marque | Sure-Lites |
| Nom du modèle | APC7RG Case Pack |
| Numéro de pièce | APC7RG |
| Matériel | High-impact, UV resistant thermoplastic (Polycarbonate) |
| Couleur | White finish, Red/Green selectable light |
| Dimensions du produit (L x l x H) | 16.57" x 2.32" x 8.26" |
| Type de source lumineuse | DIRIGÉ |
| Nombre de sources lumineuses | 2 (emergency heads) |
| Quoitage | 2.01 watts |
| Luminosité | 156 lumens |
| Voltage | 120 volts |
| Source d'énergie | Électrique avec fil |
| Type de batterie | Nickel Cadmium (NiCAD) |
| Average Battery Life (Emergency Run Time) | 90 minutes |
| Egress Coverage | Jusqu'à 17 pieds |
| Type d'installation | Flush Mount (Universal J-box) |
| Certifications | UL 924, NEC, NFPA101, NFPA70, CEC Title 20 compliant, Damp Emplacement répertorié |
| Poids de l'article | 21.4 livres (pour un paquet de 8) |
9. Garantie et assistance
9.1 Informations sur la garantie
The Sure-Lites All-Pro APC7RG unit comes with a 5-year limited warranty. The NiCad battery carries a seven-year pro-rated warranty. Please refer to the warranty documentation included with your purchase for full terms and conditions.
9.2 Assistance clientèle
For technical assistance, replacement parts, or warranty claims, please contact Sure-Lites customer support. Contact information can typically be found on the manufacturer's website ou sur l'emballage du produit.