Sure-Lites CU2-LED

Sure-Lites CU2-LED Integrated LED Emergency Light User Manual

Model: CU2-LED

1. Introduction

This manual provides detailed instructions for the installation, operation, and maintenance of the Sure-Lites CU2-LED Integrated LED Emergency Light. This unit is designed to provide reliable emergency illumination in various commercial and industrial settings.

Sure-Lites CU2-LED Emergency Light, front view

Figure 1: Sure-Lites CU2-LED Emergency Light, front view. This image shows the compact, white housing of the emergency light with its two integrated LED light heads.

Caractéristiques principales :

  • Reliable Emergency Lighting: Equipped with long-life LEDs and proprietary optics for optimal illumination during power outaget.
  • Installation facile : Features a patented EZ Hang design for quick and simplified mounting, reducing installation time.
  • Advanced Circuitry: Comprend un double volumetage AC input (120/277V), a brownout circuit, low voltage disconnect, and overload/short circuit protection.
  • Conception durable : Constructed from injection-molded, color-stable, high-impact thermoplastic, suitable for both ceiling and wall mount applications.
  • Nickel-Cadmium Battery: Integrated sealed nickel-cadmium battery provides backup power.
  • Conformité: UL924 listed and compliant with most state and local codes, including Damp Location, Life Safety NFPA 101, and NEC/OSHA.

2. Consignes de sécurité importantes

AVERTISSEMENT : Risque de choc électrique. Coupez l’alimentation avant toute installation ou intervention.

  • Read all instructions carefully before installing or servicing this fixture.
  • Ensure the main power supply is disconnected at the fuse or circuit breaker before installation or maintenance.
  • L'installation et l'entretien doivent être effectués uniquement par du personnel qualifié.
  • Ne pas monter à proximité de radiateurs à gaz ou électriques.
  • Do not use outdoors. This unit is designed for indoor use in damp emplacements.
  • Ne laissez pas les cordons d’alimentation toucher des surfaces chaudes.
  • Do not block the light output of the LED heads.
  • The battery is a sealed nickel-cadmium type. Do not attempt to open or replace with non-approved batteries.
  • Ensure all connections are secure and correct to prevent fire or electric shock.

3. Instructions d'installation

3.1 Déballage et inspection

Carefully unpack the fixture and inspect for any damage. Retain all packing materials in case of return. Ensure all components listed in the packaging are present.

3.2 Emplacement de montage

Select a suitable mounting location on a wall or ceiling. The unit is designed for universal J-box mounting patterns and includes keyhole mounting slots. Ensure the location allows for proper illumination of the egress path.

Sure-Lites CU2-LED Emergency Light dimensions diagram

Figure 2: Dimensions of the CU2-LED Emergency Light. The diagram shows the unit's length as 11 1/8 inches (282.6mm), width as 1 3/4 inches (45.0mm), and height as 5 3/8 inches (136.6mm).

3.3 Mounting the Back Plate

  1. Disconnect AC power to the junction box.
  2. Separate the front housing from the back plate. The unit is delivered with the mounting plate installed. Use a flat blade screwdriver in the designated slots to carefully pry open the unit.
  3. Position the back plate over the junction box. The back plate has multiple pre-drilled holes to accommodate various junction box configurations. Select the appropriate holes that align with your junction box.
  4. Secure the back plate to the junction box using appropriate screws (not included, typically provided with the junction box). Ensure the back plate is firmly attached to prevent movement.
  5. For hands-free wiring, utilize the EZ Hang feature. The back plate includes a tab and slot mechanism. Carefully insert the tab from the front housing into the corresponding slot on the back plate. This allows the front housing to hang while electrical connections are made.
Sure-Lites CU2-LED Emergency Light internal wiring

Figure 3 : Interne view of the CU2-LED Emergency Light showing wiring and battery. This image displays the circuit board, battery pack, and wiring connections, including the 120VAC input wire.

3.4 Connexions électriques

The unit supports dual voltage AC input (120V or 277V). Identify the correct voltage pour votre installation.

  • Connectez le NOIR fil reliant le luminaire au 120V AC LINE fil.
  • Connectez le ORANGE fil reliant le luminaire au 277V AC LINE fil.
  • Connectez le BLANC fil reliant le luminaire au NEUTRE fil.
  • Assurez-vous d'une mise à la terre correcte conformément aux normes électriques locales.
  • Use appropriate wire nuts for all connections. Ensure connections are tight and secure.
  • After wiring, connect the battery pack to the circuit board. The battery connector is typically a small plug that fits into a corresponding receptacle on the PCB. Ensure it is fully seated.

IMPORTANT: Do not connect both 120V and 277V line wires simultaneously. Cap off the unused line wire with a wire nut.

3.5 Assemblage final

  1. Once all electrical connections are made and the battery is connected, carefully tuck all wires into the junction box.
  2. Align the front housing with the mounted back plate. Gently push the front housing onto the back plate until it snaps securely into place. Ensure there are no gaps between the housing and the mounting surface.
  3. Restore AC power to the circuit. The charge indicator light (usually an LED on the unit's housing) should illuminate, indicating the battery is charging.

4. Fonctionnement

4.1 Opération initiale

Upon initial power-up, allow the unit to charge for a minimum of 24 hours before conducting any tests. This ensures the nickel-cadmium battery reaches its full capacity.

4.2 Fonctionnement automatique

The Sure-Lites CU2-LED Emergency Light is designed for automatic operation. When AC power is present, the unit's battery will charge, and the LED heads will remain off. In the event of an AC power failure or a significant voltage drop (brownout circuit activation), the unit will automatically switch to battery backup, illuminating the LED heads to provide emergency lighting.

Le faible voltage disconnect feature protects the battery from deep discharge, extending its lifespan.

4.3 Bouton d'essai

A test button is located on the unit's housing. Pressing and holding this button simulates an AC power failure, causing the LED heads to illuminate (if the battery is charged). Release the button to return to normal operation. This button is used for routine testing.

5. Entretien

5.1 Tests de routine

Regular testing is crucial to ensure the emergency light functions correctly during an actual power outage. Follow these guidelines:

  • Mensuel: Press the test button for at least 30 seconds. The LED heads should illuminate. Release the button; the LED heads should turn off, and the charge indicator should remain lit.
  • Annuellement: Disconnect AC power to the unit for a full 90 minutes. The LED heads should remain illuminated for the entire duration. Reconnect AC power; the LED heads should turn off, and the charge indicator should remain lit.

Keep a record of all tests for compliance purposes.

5.2 Informations sur la batterie

The unit contains a sealed nickel-cadmium battery. This battery requires a full recharge time of 24 hours (max.) at 120/277V or 48 hours at 240V after a discharge event. The battery is designed for long life but will eventually require replacement.

WARNING: Battery replacement should only be performed by qualified service personnel. Use only approved replacement batteries from Sure-Lites to ensure proper operation and safety.

To access the battery for replacement, the front housing must be carefully separated from the back plate using a flat blade screwdriver in the designated slots, similar to the initial installation process. Exercise caution to avoid damaging internal components.

5.3 Nettoyage

Nettoyez périodiquement l'extérieur de l'appareil avec un chiffon doux et sec.amp cloth. Do not use abrasive cleaners or solvents, as these can damage the housing.

6. Dépannage

Problème Cause possible Solution
LED heads do not illuminate during a power outage or when test button is pressed.
  • No AC power to the unit.
  • Battery not connected or faulty.
  • La batterie n'est pas complètement chargée.
  • Faulty LED heads or circuit board.
  • Vérifiez le disjoncteur et les connexions électriques.
  • Ensure battery is properly connected. Allow 24 hours for initial charge.
  • Perform a 24-hour recharge.
  • Contactez un personnel de service qualifié.
Le voyant de charge est éteint.
  • No AC power to the unit.
  • Faulty charge indicator LED.
  • Défaut de circuit interne.
  • Check AC power supply and wiring.
  • Contactez un personnel de service qualifié.
LED heads blink when test button is pressed, but do not stay on.
  • Battery has insufficient charge.
  • La batterie est en fin de vie.
  • Allow unit to charge for 24-48 hours.
  • Consider battery replacement by qualified personnel.
Unit does not snap securely onto mounting plate.
  • Wires are obstructing the closure.
  • Mounting plate screws are too tight, causing distortion.
  • Carefully arrange wires within the junction box.
  • Slightly loosen mounting plate screws if necessary, then re-tighten after housing is secured.

7. Spécifications

Numéro de modèleCU2-LED
MarqueSure-Lites
Source de lumièreLED intégrée
Voltage120/277 Volts AC (Dual Voltage)
Type de batterieSealed Nickel-Cadmium (Ni-Cd)
Temps de recharge24 hours (max.) at 120/277V; 48 hours at 240V
MatérielHigh-impact Thermoplastic
CouleurBlanc
Type de montageMontage mural, montage au plafond
Dimensions (L x l x H)11.13" x 1.75" x 5.37" (282.6 mm x 45.0 mm x 136.6 mm)
Poids1.21 livres
CertificationsUL924 Listed, Damp Location, NFPA 101, NEC/OSHA Compliant
FabricantDivision Éclairage d'Eaton

8. Informations sur la garantie

The Sure-Lites CU2-LED Emergency Light comes with a garantie limitée de cinq ans from the manufacturer, Eaton Lighting Division. This warranty covers defects in materials and workmanship under normal use and service.

For specific warranty terms, conditions, and claim procedures, please refer to the official warranty documentation provided with your product or contact Sure-Lites customer support.

9. Assistance clientèle

If you encounter any issues or have questions regarding the installation, operation, or maintenance of your Sure-Lites CU2-LED Emergency Light that are not covered in this manual, please contact Sure-Lites customer support or visit their official website pour une assistance supplémentaire.

For the most up-to-date contact information, please refer to the product packaging or the Sure-Lites official website.